Electromagnetic Interference

ANSI/TIA/EIA-569-A
Design Considerations


1.
Purpose of the ANSI/TIA/EIA-569-A Standard
2.
Service Entrance Pathways
3.
Entrance Facilities
4.
Equipment Room
5.
Intrabuilding Backbone Pathways
6.
Telecommunications Closet
7.
Horizontal Pathways
8.
Consolidation Points
9.
Electromagnetic Interference
10.
Firestops

9. Electromagnetic Interference

Voice and data telecommunications cabling should not be run adjacent and parallel to power cabling-even along short distances-unless one or both cable types are shielded and grounded. For low-voltage communication cables, a minimum 5-inch distance is required from any fluorescent lighting fixture or power line over 2 kVA and up to 24 inches from any power line over 5 kVA*. In general, telecommuni-cations cabling is routed separately, or several feet away from power cabling. Similarly, telecommunications cabling is routed away from large motors, generators, induction heaters, arc welders, x-ray equipment, and radio frequency, microwave or radar sources.

*Note: Distance recommendations from (1990) TIA/EIA-569 are reproduced here by popular request. For current recommendations, refer to NEC/NFPA 70, Article 800-52.